10cas

10cas is ready to accept up to two 0-10VDC signals, and command a Casambi network, presenting themselves as two Switch controls with full range 0-100% dimming.

10cas has programmable separate channel high and low trim values to allow for setting the bottom and top analog input voltage, to Casambi 0% and 100% levels. In addition, each channel has a hysteresis to allow for interfacing with noisy analog signals to keep such signals from causing flicker on the network.

Read more

Input
Voltage range: 12-24 VDC, Class 2
No-load input current: 30 mA

0-10VDC Input (A and B)
2-wire analog 0-10VDC, two channels
1mA source current, input must sink for control
Top and bottom “trim” and hysteresis user programmable

Relay control output
Output voltage: 12-24 VDC, same as input
Max. output current: 100 mA