Casambi LCM 10

The LCM ( lighting Controls Module) based on the Casambi Salvador 16 address module. It can control up to 15 sub address DALI luminaires. It has 10 ports, with each port having a permanent live, an emergency live, which can be switched off for testing, DALI+ and DALI-,Neutral, and Earth.

The emergency test relay can be activated via a hard wired emergency test input for use with a fish key, or over the Casambi network where it will appear on the app as a relay.

The enclosure has been designed for ease of installation with ‘Z’ bolt fixing rails on the rear. All the connections to the unit can also be pre-wired before installation.

  • 10 x 6 pole sockets to connects luminaires
  • 2 pole input for emergency testing
  • The LCM is not powered from the bus and requires a permanent mains supply from the relevant lighting circuit
  • Maximum Range Line of sight of 200m and 50m max if obstructed
  • Requires 6 pole plugs for luminaire wiring
  • Inputs 1 Emergency
  • DALI output 15 DALI addresses
  • Radio transceiver
  • Operating Frequencies 2402…2480 MHz
  • Maximum Power Output +8 dBm
  • Luminaire connection 6 way , Live , Earth, Neutral, Emergency Live, DALI-, DALI +
  • Degree of Protection IP20 ( indoor use only)
  • Supply voltage 90-240 V AC 50Hz
  • Power consumption Off load – 1.2 watts
  • All channels on – 4 watts
  • Internal fuse 1AT
  • Load (total) 10A
  • Load per channel 6A
  • Case material Flame Retardant ABS
  • Operating temperature -10 to +50°C
  • Max Humidity 90% RH non-condensing

Read More